# Compatibility research and testing scope

Research date: 11 November 2026. All named meter/product examples are documentation-based interface examples, not claims of Busrelix hardware testing.

| Meter class | Typical exposed data | Requirement |
|---|---|---|
| Water / hot water | accumulated volume, flow, alarms/status | wired M-Bus module and enabled records |
| Heat / cooling | energy, volume, flow, power, temperatures | model's supported variable-data telegram |
| Electricity | energy, power and optionally voltage/current | wired M-Bus communication module |
| Gas | volume, flow and model-specific status | wired M-Bus interface; observe meter read-frequency limits |
| Pulse converter | pulse counts / scaled consumption | proper channel/unit configuration in device |
| Other M-Bus sensors | decoded standard DIF/VIF records or raw unknown fields | manufacturer documentation |

Primary references:
- Relay MR003 USB manual (2017 v1.2): https://service.relay.de/media/manuals/MR003USB_DE.pdf — USB virtual COM, 8E1-compatible M-Bus master, 300–9600 baud, 10 unit loads. The product-page technical table has a narrower inconsistent speed range; the actual manual is used.
- Relay product/driver page: https://www.relay.de/en/products/m-bus-master/mikro-master
- Silicon Labs VCP prerequisite: https://www.silabs.com/software-and-tools/usb-to-uart-bridge-vcp-drivers
- OMS Guide to Wired M-Bus Installations, TR09 v1.0.3: https://oms-group.org/wp-content/uploads/2024/05/OMS-TR09_Guide_to_Wired_M-Bus_Installations_v_1.0.3-2.pdf
- OMS Wired M-Bus TR02 v2.0.3: https://oms-group.org/wp-content/uploads/2024/05/OMS-TR02_Wired_M-Bus_v2.0.3.pdf
- Kamstrup documented example with primary/ID/date-time/pulse settings: https://www.kamstrup.com/en-en/product-centre/mbus-alternative-registers
- OpenMUC jMBus user guide (independent implementation guidance, no library code used): https://www.openmuc.org/mbus/user-guide/
- Historical M-Bus Usergroup explanations used only as legacy reference, not a current conformity specification: https://m-bus.com/documentation-wired/05-data-link-layer, /06-application-layer, /07-network-layer and /08-appendix. These pages explicitly describe an older specification. The implementation does not claim current EN 13757 or OMS certification; further vendor/conformance testing is required.

Supported: validated FT1.2 E5/long response frames; primary discovery; full-ID and wildcard secondary search (including mode-2); variable data (CI72/76), integer, Float32, BCD, common LVAR, date/time, standard units, voltage/current extension; DIF/DIFE storage/tariff/subunit; continuation reads bounded by max pages; raw manufacturer tails. Legacy CI73/77 counters decode common units and shared historic units; unsupported unit codes remain raw. Unknown VIF/VIFE, protected/encrypted and compact application frames are explicit limitations.

Write support: standard primary-address record and eight-digit secondary-ID record; exact documented numeric/date/time record encoding. User confirmation, identity recheck, destination check, no broadcast writes, no automatic write retry, acknowledgement and readback handled separately. This does not bypass vendor access protection or establish universal writability.

Hardware inspected: local Relay M-Bus Micro-Master USB, VID_10C4 PID_EA60, Windows problem code 28, no assigned COM port. No driver installed and no physical meter connected. Tests use independent frame vectors and a two-meter simulator including collisions, duplicate primary addresses, stale values, occupied destination, rejected/lost-ACK writes, mode-2 and readback verification. These checks do not validate the adapter's physical signal/timing or a particular meter's firmware behaviour.